S8-200AGM-RE |
S8-200AGM-RE |
|
|
| Series | VRLA AGM-S | Warranty | See Warranty Terms |
|---|---|---|---|
| Volts | 8 | Design | GC8T |
| Cells | 4 | ||
| Terminal Type | F14(M8) and TP08 Adapter [+21mm] | ||
| Included Hardware | M8 stainless bolts & washers & TP08 adapter | ||
| Size & Thread | M8 | ||
| Charge | Discharge | |
|---|---|
| Charge Voltage Range | 2.45 V/cell @ 25°C (77°F) |
| Float Voltage Range | 2.3 V/cell @ 25°C (77°F) |
| Recommended Charge Current | 35 A |
| Maximum Charge Current | 50 A |
| Self-Discharge Rate | Less than 2% per month at 25°C (77°F) |
| Internal Resistance | 3.2 mΩ |
| Capacity | |
|---|---|
| Cold Crank Amps (CCA) 0°F / -18°C | 680 |
| Capacity Affect by Temperature | 40°C (104°F) |
25°C (77°F) |
0°C (32°F) |
-15°C (5°F) |
|---|---|---|---|---|
| 102% | 100% | 85% | 65% |
| Hour Rate | Capacity / AMP Hour | Current / AMPs |
|---|---|---|
| @ 100 Hour Rate | 200 AH | 2.0 A |
| @ 20 Hour Rate | 170 AH | 8.5 A |
| @ 10 Hour Rate | 162 AH | 16.2 A |
| @ 5 Hour Rate | 150 AH | 29.9 A |
| Cut Off Voltage | Constant Current Discharge | |||||||
|---|---|---|---|---|---|---|---|---|
| VPC | 1 hr | 2 hr | 3 hr | 4 hr | 5 hr | 6 hr | 8 hr | 10 hr |
| 95 | 57.2 | 43.9 | 35.1 | 29.9 | 25 | 19.9 | 16.6 | |
| Specifications | |||
|---|---|---|---|
| Weight | 34.5 kg | 76 lbs | |
| Length | 260 mm | 10.24" | |
| Width | 182 mm | 7.17" | |
| Height Incl. Term. | 300 mm | 11.81" | |
| Product measurements & weights are calculated based on sample data. Individual specifications are subject to vary due to the manufacturing process & battery components. | |||
| Container | ABS | ||
|---|---|---|---|
| Cover | ABS | ||
| Handles | Nylon Strap | ||
Cycle Life vs. Depth of Discharge
Capacity vs. Temperature