Skip to main content

FLOODED DEEP CYCLE BATTERY

S2 L16-EX

Series 4500 Warranty 4 Years
Volts 2 BCI L16
Cells 1 Plates/Cell 29
Terminal Type LT
Included Hardware S/S Hex Cap Screw, Nut, Lock & Flat Washer
Size & Thread 5/16"-18
Cables Optional: 19" 4/0 interconnect cable
Charge
Charge Voltage Range 2.45-2.5 V/cell @ 25°C (77°F)
Float Voltage Range 2.25 V/cell @ 25°C (77°F)
Recommended Charge Current 120 A
Maximum Charge Current 200 A
Self-Discharge Rate 5%-10% per month at 25°C (77°F)
Capacity
Cold Crank Amps (CCA) 0°F / -18°C 2438
Marine Crank Amps (MCA) 32°F / 0°C 3048
Reserve Capacity (RC @ 25A) 2496 Minutes
Reserve Capacity (RC @ 75A) 832 Minutes
Capacity Affect by Temperature 40°C
(104°F)
25°C
(77°F)
0°C
(32°F)
-15°C
(5°F)
105% 100% 75% 50%
Hour Rate Capacity / AMP Hour Current / AMPs
@ 100 Hour Rate 1342 AH 13.42 A
@ 72 Hour Rate 1269 AH 17.62 A
@ 50 Hour Rate 1201 AH 24.02 A
@ 20 Hour Rate 1040 AH 52.00 A
@ 15 Hour Rate 967 AH 64.48 A
@ 10 Hour Rate 926 AH 92.56 A
@ 8 Hour Rate 894 AH 111.80 A
@ 5 Hour Rate 832 AH 166.40 A
@ 1 Hour Rate 468 AH 468.00 A

Ampere hour capacity ratings based on specific gravity of 1.280 at 27°C (80°F).
Reduce capacities 5% for specific gravity of 1.265 and 10% for 1.250.

Specifications
Weight 58 kg 128 lbs
Length 31.8 cm 12.5"
Width 18.1 cm 7.13"
Height Inc. Term. 43.2 cm 17"
Product measurements & weights are calculated based on sample data. Individual specifications are subject to vary due to the manufacturing process & battery components.
Electrolyte Reserve 57 mm 2.25"
Container High Density Polypropylene
Cover High Density Polypropylene
Handles Rope / Plastic Handle

Cycle Life vs. Depth of Discharge

Voltage vs. Depth of Discharge

Detailed Illustration

Rev.#2 | May 2019