FLOODED DEEP CYCLE BATTERY

6 FS 400

Series FS Warranty 1 Year
Volts 6 BCI L16
Cells 3 Plates/Cell 17
Terminal Type DT
Included Hardware S/S Hex Cap Screw, Nut, Lock & Flat Washer
Size & Thread 5/16"-18 x 1-1/2"
Cables Optional: 19" 4/0 interconnect cable
Charge
Charge Voltage Range 2.45-2.5 V/cell @ 25°C (77°F)
Float Voltage Range 2.25 V/cell @ 25°C (77°F)
Self-Discharge Rate 5%-10% per month at 25°C (77°F)
Capacity
Cold Crank Amps (CCA) 0°F / -17°C 968
Marine Crank Amps (MCA) 32°F / 0°C 1209
Reserve Capacity (RC @ 25A) 960 Minutes
Reserve Capacity (RC @ 75A) 239 Minutes
Hour Rate Capacity / AMP Hour Current / AMPs
@ 100 Hour Rate 532 AH 5.32 A
@ 75 Hour Rate 504 AH A
@ 50 Hour Rate 476 AH 9.52 A
@ 20 Hour Rate 400 AH 20 A
@ 15 Hour Rate 380 AH 25.33 A
@ 10 Hour Rate 352 AH 35.2 A
@ 8 Hour Rate 344 AH 43 A
@ 5 Hour Rate 316 AH 63.2 A
@ 1 Hour Rate 160 AH 160 A

Amphere hour capacity ratings based on specific gravity of 1.280.
Reduce capacities 5% for specific gravity of 1.265 and 10% for 1.250.

Specifications
Weight 54 kg 119 lbs
Length 31.8 cm 12.5"
Width 18.1 cm 7.13"
Height Inc. Term. 42.5 cm 16.75"
Product measurements & weights are calculated based on sample data. Individual specifications are subject to vary due to the manufacturing process, battery components & electrolyte levels.
Electrolyte Reserve 57 mm 2.25"
Container Polypropylene
Cover Polypropylene
Handles Rope / Plastic Handle

Cycle Life vs. Depth of Discharge

Voltage vs. Depth of Discharge

Rev.#3 | May 2018