FLOODED DEEP CYCLE BATTERY

2 YS 62P

Series 5000 Warranty 10 Years
Volts 2 BCI SPEC
Cells 2 Plates/Cell 31
Terminal Type Flag
Included Hardware S/S Hex Cap Screw, Nut, Lock & Flat Washer
Size & Thread 5/16"-18 x 1-1/2"
Cables 19" 4/0 interconnect cables *RE incl.
Charge
Charge Voltage Range 2.45-2.5 V/cell @ 25°C (77°F)
Float Voltage Range 2.25 V/cell @ 25°C (77°F)
Self-Discharge Rate 5%-10% per month at 25°C (77°F)
Capacity
Cold Crank Amps (CCA) 0°F / -17°C 5741
Marine Crank Amps (MCA) 32°F / 0°C 7176
Reserve Capacity (RC @ 25A) 11664 Minutes
Reserve Capacity (RC @ 75A) 3888 Minutes
Hour Rate Capacity / AMP Hour Current / AMPs
@ 100 Hour Rate 6853 AH 68.53 A
@ 75 Hour Rate 5042 AH 70.02 A
@ 50 Hour Rate 4663 AH 93.25 A
@ 20 Hour Rate 4860 AH 243 A
@ 15 Hour Rate 4520 AH 301.32 A
@ 10 Hour Rate 4034 AH 403.38 A
@ 8 Hour Rate 3791 AH 473.85 A
@ 5 Hour Rate 3256 AH 651.24 A
@ 1 Hour Rate 1652 AH 1652.4 A

Amphere hour capacity ratings based on specific gravity of 1.280.
Reduce capacities 5% for specific gravity of 1.265 and 10% for 1.250.

Specifications
Weight 258.5 kg 570 lbs
Length 69.5 cm 27.38"
Width 22.9 cm 9"
Height Inc. Term. 80.3 cm 3163"
Product measurements & weights are calculated based on sample data. Individual specifications are subject to vary due to the manufacturing process, battery components & electrolyte levels.
Electrolyte Reserve 95 mm 3.75"
Container (Inner) Polypropylene
Cover (Inner) Polypropylene - heat sealed to inner container
Container (Outer) High Density Polyethylene
Cover (Outer) High Density Polyethylene snap fit to outer container
Handles Molded

Cycle Life vs. Depth of Discharge

Voltage vs. Depth of Discharge

Rev.#3 | May 2018